Article Abstract

A lack of available information on heating, ventilation, and air-conditioning (HVAC) systems can affect the performance of data-driven fault-tolerant control (FTC) models. This study proposed an in situ selective incremental calibration (ISIC) strategy. Faults were introduced into the indoor air (Ttz1) thermostat and supply air temperature (Tsa) and chilled water supply air temperature (Tchws) sensors of a central air-conditioning system. The changes in the system performance after FTC were evaluated. Then, we considered the effects of the data quality, data volume, and variable number on the FTC results. For the Ttz1 thermostat and Tsa sensor, the system energy consumption was reduced by 2.98% and 3.72% with ISIC, respectively, and the predicted percentage dissatisfaction was reduced by 0.67% and 0.63%, respectively. Better FTC results were obtained using ISIC when the Ttz1 thermostat had low noise, a 7-day data volume, or sufficient variables and when the Tsa and Tchws sensors had low noise, a 14-day data volume, or limited variables.

Download full-text PDF

Source
http://www.ncbi.nlm.nih.gov/pmc/articles/PMC10891601PMC
http://dx.doi.org/10.3390/s24041150DOI Listing

Publication Analysis

Top Keywords

ttz1 thermostat
12
data volume
12
fault-tolerant control
8
central air-conditioning
8
supply air
8
air temperature
8
tchws sensors
8
low noise
8
data
5
study sensor
4

Similar Publications

A lack of available information on heating, ventilation, and air-conditioning (HVAC) systems can affect the performance of data-driven fault-tolerant control (FTC) models. This study proposed an in situ selective incremental calibration (ISIC) strategy. Faults were introduced into the indoor air (Ttz1) thermostat and supply air temperature (Tsa) and chilled water supply air temperature (Tchws) sensors of a central air-conditioning system.

View Article and Find Full Text PDF